CLY713U-BR
Type: | 2-wire smoke detector with remote LED output |
Item no.: | WT631-2L |
Operating voltage: | DC (10 ~ 33) V |
Start-up current: | ≤ 750 μA |
Start-up time: | ≤ 10 s |
Quiescent current: | ≤ 45 μA |
Alarm current (max): | 20 mA (without remote LED) @ 10 V |
24 mA (with remote LED) @ 10 V | |
75 mA (without remote LED) @ 28 V | |
97 mA (with remote LED) @ 28 V | |
62 mA (without remote LED) @ 24 V | |
81 mA (with remote LED) @ 24V | |
Maximum permitted current: | 100 mA without remote LED |
Sampling time: | 4 s |
Reset voltage: | ≤ 2.1 V |
Reset time: | ≤ 3 s |
Smoke sensitivity: | (0.08 ~ 0.14) dB/m |
Operating temperature: | -10°C to +50°C |
Operating humidity: | (0 ~ 95)% RH, non-condensing |
Storage temperature: | -25°C to +80°C |
Storage humidity: | (0 ~ 98)% RH, non-condensing |
Alarm indicator: | Two continuous emitting red LEDs |
Dimensions (excluding contacts): | (Φ100 × 34) mm |
Weight (excluding contacts): | ? g |